Pepperl+Fuchs
KFA5-SR2-Ex.2 Switch Amplifier
2-channel isolated barrier
• 115 V AC supply
• Dry contact or NAMUR inputs
• Relay contact output
• Line fault detection (LFD)
• Reversible mode of operation
• Up to SIL2 acc. to IEC 61508/IEC 61511
This isolated barrier is used for intrinsic safety applications.
It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.
It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area.
The proximity sensor or switch controls a form C changeover
relay contact for the safe area load.
The normal output state can be reversed using switches S1 and S2. Switch S3 is used to enable or disable line fault detection of the field circuit.
The normal output state can be reversed using switches S1 and S2. Switch S3 is used to enable or disable line fault detection of the field circuit.
During an error condition, the relays revert to their
deenergized state and the LEDs in dicate the fault according to
NAMUR NE44.